Transformer Winding Losses Evaluation when Supplying Non Linear Load - Archive ouverte HAL Accéder directement au contenu
Communication Dans Un Congrès Année : 2009

Transformer Winding Losses Evaluation when Supplying Non Linear Load

Résumé

Nonlinear loads produce harmonic currents, which induce additional losses in transformers and cause temperature rise, especially in the windings. The estimation of winding eddycurrent loss, in the presence of harmonics, is based on the knowledge of winding eddy-current loss at power frequency. This paper deals with the transformer winding loss estimation and gives a simplified winding resistance expression that takes winding eddy-current into account and allows to estimate associated losses. The impact of transformer winding characteristics, as conductor size and layer number, on the resistance variation with frequency is shown.
Fichier principal
Vignette du fichier
Transformer_Winding_Losses_Evaluation_when_Supplying_Non_Linear_Load.pdf (174.44 Ko) Télécharger le fichier
Origine : Fichiers produits par l'(les) auteur(s)
Loading...

Dates et versions

hal-00422449 , version 1 (07-10-2009)

Identifiants

  • HAL Id : hal-00422449 , version 1

Citer

Wilfried Frelin, Luc Berthet, Marc Petit, Jean-Claude Vannier. Transformer Winding Losses Evaluation when Supplying Non Linear Load. The 44th International Universities' Power Engineering Conference - UPEC 2009, Sep 2009, Glasgow, United Kingdom. pp.CD-Rom Proceedings. ⟨hal-00422449⟩
62 Consultations
304 Téléchargements

Partager

Gmail Facebook X LinkedIn More